Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - MEANS OF EGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/09/2008 | VIOL - MEANS OF EGRESS | Correction Required | TFC 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source, shall have an intensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose. _____1. The exit sign located in the dinning area shall be illuminated at all times. _____2. The exit sign located in the kitchen shall be illuminated at all times. |
|
| 07/09/2008 | VIOL - MEANS OF EGRESS | Correction Required | TFC 1027.4 Power source. Where emergency illumination is required in Section 1027.5, exit signs shall be visible under emergency illumination conditions. _____1. Repair the broken emergency lighting unit located in the kitchen. |