Case: T08FR01839
Case Details
Entered Date:
07/09/2008
Applicant:
GRANT & SILVERBELL LLC
Description:
Full Fire Prevention Inspection. Issi Franco 750-9780
Outstanding Inspections
Case Number: T08FR01839
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/09/2008 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.4 Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. _____1. Remove the cube adapter located by the drive-thru window and replace it with a fused multi-plug adapter. |
| 07/09/2008 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. _____1. Replace the missing electrical outlet cover located in the dinning area behind the sticker and ball machines. _____2. Replace the broken electrical light switch cover located in the men's restroom. _____3. Replace the missing electrical outlet cover located in the office. _____4. Replace the missing electrical outlet cover located above the cutting/prep table. _____5. Replace the missing electrical outlet cover for the oulet that powers the microwave. |
| 07/09/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____1. Service, test and tag the hood extinguishing system or provide documentation of such work being done within the last 6 months. |
| 07/09/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. _____1. Clean and remove all grease accumulation from the hood system and provide documentation of the work performed. ________________________________________________ (John E. Bieg, Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Full inspection done by Inspector John E. Bieg Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. Thank you. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg |
| 07/09/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source, shall have an intensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose. _____1. The exit sign located in the dinning area shall be illuminated at all times. _____2. The exit sign located in the kitchen shall be illuminated at all times. |
| 07/09/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.4 Power source. Where emergency illumination is required in Section 1027.5, exit signs shall be visible under emergency illumination conditions. _____1. Repair the broken emergency lighting unit located in the kitchen. |
| 07/09/2008 | VIOL - COMPRESSED GASES | JBURGE | Correction Required | TFC 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. _____1. Secure the compressed gas cylinders located in the kitchen to a wall or fixed object with a chain or strap. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR01839
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/21/2008 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected. |