Case: T08FR01671

Parcel: 11516024A


Addresses:

2165 N FORBES BL

Inspection Status: Compliance

Inspection History: INSP - FULL

Date Description Inspector Results Comments
06/24/2008 INSP - FULL Compliance 1) THE SYSTEM SIDE GUAGE ON THE RISER IS CORRODED AND NEEDS TO CHANGED OUT

2) SIERRA TILE - THE PROPERTY WAS SECURED AND UNABLE TO INSPECT. THE SPRINKLER DEFICIENCY REPORT STATES THAT A SPRINKLER IS BLOCKED BY A PILLER. ALSO THE CONTROL VALVE IS TO BE SECURED WITH A LOCK AND CHAIN OR ELECTRONICALLY SUPERVISED. PLEASE NOTE THAT THE SIERRA TILE SUITE HAS CENTRAL GB SPRINKLERS THAT WERE ON A RECALL AND NEED TO BE REPLACED. FOR INFORMATION CALL 1-800-505-8553. THERE ARE ALSO NUMEROUS ESUTCHEONS MISSING THROUGH THE PROPERTY.