Inspection Status: Compliance
Inspection History: INSP - FULL
Case Number - T08FR01671
Inspection Description - INSP - FULL
Inspection Status - Compliance
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/24/2008 | INSP - FULL | Compliance | 1) THE SYSTEM SIDE GUAGE ON THE RISER IS CORRODED AND NEEDS TO CHANGED OUT 2) SIERRA TILE - THE PROPERTY WAS SECURED AND UNABLE TO INSPECT. THE SPRINKLER DEFICIENCY REPORT STATES THAT A SPRINKLER IS BLOCKED BY A PILLER. ALSO THE CONTROL VALVE IS TO BE SECURED WITH A LOCK AND CHAIN OR ELECTRONICALLY SUPERVISED. PLEASE NOTE THAT THE SIERRA TILE SUITE HAS CENTRAL GB SPRINKLERS THAT WERE ON A RECALL AND NEED TO BE REPLACED. FOR INFORMATION CALL 1-800-505-8553. THERE ARE ALSO NUMEROUS ESUTCHEONS MISSING THROUGH THE PROPERTY. |