Case Details

Status:

FIELD

Type:

INSPECTION
Address:

Entered Date:

06/24/2008

Applicant:

FORBES TUCSON LLC

Description:

SPRINKLER INSPECTION

Completed Inspections

Case Status: FIELD
Case Number: T08FR01671
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
06/24/2008 INSP - FULL EDESCHAI Approved 1) THE SYSTEM SIDE GUAGE ON THE RISER IS CORRODED AND NEEDS TO CHANGED OUT 2) SIERRA TILE - THE PROPERTY WAS SECURED AND UNABLE TO INSPECT. THE SPRINKLER DEFICIENCY REPORT STATES THAT A SPRINKLER IS BLOCKED BY A PILLER. ALSO THE CONTROL VALVE IS TO BE SECURED WITH A LOCK AND CHAIN OR ELECTRONICALLY SUPERVISED. PLEASE NOTE THAT THE SIERRA TILE SUITE HAS CENTRAL GB SPRINKLERS THAT WERE ON A RECALL AND NEED TO BE REPLACED. FOR INFORMATION CALL 1-800-505-8553. THERE ARE ALSO NUMEROUS ESUTCHEONS MISSING THROUGH THE PROPERTY.