Case: T08FR01528

Parcel: 13316031C

Inspection Status: Compliance

Inspection History: INSP - FULL

Date Description Inspector Results Comments
06/16/2008 INSP - FULL Compliance 901.6 Fire protection systems maintenance

1) N/E office and hallway, sprinklers are closer togeather than 6'
N/E entry, a closet does not have sprinkler coverage
N/E offices, (glass block walls) 1 room relocate 1 head, 1 room
add 3 sprinklers

2) Suite 310 East side open area, heads are closer than 6'

3) Suite 240 Inadequate coverage, add 2 sprinklers by glass doors

4) Suite 220 Phone closet, add sprinklers as required

5) Suite 210 Sprinklers exceed the max. of 7' 6" off walls

6) Suite 110 Add sprinkler protection to the long hall, Laurers office
Sprinkler head is 11' off a wall

7) 2nd. floor out side of restrooms, a concealed sprinkler is painted
and the frame work is missing

8) 3rd. floor roof access, a pendent sprrinkler head is in the upright
position

9) The sprrinkler system is due for the 5 year internal inspection,
and the guages should be calibrated

Submittals for the required work shall be made with in 14 days and work completed within 30 days