Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Case Details

Status:

FIELD

Type:

INSPECTION

Entered Date:

06/16/2008

Applicant:

ROBEN FAMILY LTD PTNERSHP LP

Description:

Sprinkler inspection

Completed Inspections

Case Status: FIELD
Case Number: T08FR01528
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
06/16/2008 INSP - FULL EDESCHAI Approved 901.6 Fire protection systems maintenance 1) N/E office and hallway, sprinklers are closer togeather than 6' N/E entry, a closet does not have sprinkler coverage N/E offices, (glass block walls) 1 room relocate 1 head, 1 room add 3 sprinklers 2) Suite 310 East side open area, heads are closer than 6' 3) Suite 240 Inadequate coverage, add 2 sprinklers by glass doors 4) Suite 220 Phone closet, add sprinklers as required 5) Suite 210 Sprinklers exceed the max. of 7' 6" off walls 6) Suite 110 Add sprinkler protection to the long hall, Laurers office Sprinkler head is 11' off a wall 7) 2nd. floor out side of restrooms, a concealed sprinkler is painted and the frame work is missing 8) 3rd. floor roof access, a pendent sprrinkler head is in the upright position 9) The sprrinkler system is due for the 5 year internal inspection, and the guages should be calibrated Submittals for the required work shall be made with in 14 days and work completed within 30 days