Case: T08FR01254

Parcel: 12416017A


Addresses:

602 E 22ND ST


Inspection Status: Correction Required

Inspection History: INSP - FULL

Case Number - T08FR01254

Inspection Description - INSP - FULL

Inspection Status - Correction Required

Date Description Inspector Results Comments
05/16/2008 INSP - FULL Correction Required 1) 901.6 Where sprinklers have been in service for 50 years, they shall be replaced , or samples from one or more sample areas shall be tested.

2) 605.1 The exterior electrical outlet by the front door shall have a cover plate

3) 315.2.1 Storage shall be maintained 18" below sprinkler head deflectors

4) 901.6 The spool piece on the riser below the check valve is badly corrided and shall be replaced

5) 605.5 Extention cords shall not be used in place of permanent wiring nor run under doors

6) 315.2.3 Equipment rooms shall not be used for combustable storage

7) 703.2.2 Corridor doors shall not be blocked open

8) 315 (misc. combustable storage) The office area of
sherry is in need of housekeeping. The amount of combustables is only adding to the fire load.