Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - MEANS OF EGRESS
Case Number - T08FR01162
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/08/2008 | VIOL - MEANS OF EGRESS | Correction Required | TFC 1008.1.8.3- Locks and latches. Post a sign on the inside of the entrance doors that have a double keyed lock. The sign shall state, "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED." | |
05/08/2008 | VIOL - MEANS OF EGRESS | Correction Required | TFC 1027.5- illumination emergency power. Test all emergency lighting units and exit signs for emergency back-up power. Replace or repair defective units. | |
05/08/2008 | VIOL - MEANS OF EGRESS | Correction Required | TFC 1027.5- illumination emergency power. Repair or replace the emergency lighting unit located in the speaker room on the ceiling. | |
05/08/2008 | VIOL - MEANS OF EGRESS | Correction Required | TFC 1008.1.8- Door operations. Remove all locking bar hardware from the egress doors. Locking bar hardware is prohibited on egress doors. | |
05/08/2008 | VIOL - MEANS OF EGRESS | Correction Required | TFC 1027.5- illumination emergency power. The exit sign and emergency lighting unit located in the north exit corridor shall have emergency back-up power. |