Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

05/08/2008

Applicant:

TUCSON PLACE PARTNERS LLC

Description:

Full Inspection.

Outstanding Inspections

Case Number: T08FR01162
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 11
End Date Description Inspector Results Comments
05/08/2008 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC 510.1- Identification. Post a permanent, durable and readily visible sign on one of the double doors located in the men's restroom. The sign shall state, "SPRINKLER SYSTEM RISER INSIDE."
05/08/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.5- Extension cords. Remoe the two extension cords located in the sales development room.
05/08/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.6- Unapproved conditions. All open spaces in the electrical panels located in the stock room shall be properly covered.
05/08/2008 VIOL - FIRE RESIST.RATED CONST JBURGE Correction Required TFC 703.1- Maintenance. Replace the missing ceiling tiles located in the fire alarm control panel room.
05/08/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6- Inspection, testing and maintenance. Repair the sprinkiler system fire department connections. The connections will not swivel properly.
05/08/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8- Door operations. Remove all locking bar hardware from the egress doors. Locking bar hardware is prohibited on egress doors.
05/08/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8.3- Locks and latches. Post a sign on the inside of the entrance doors that have a double keyed lock. The sign shall state, "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED."
05/08/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.5- illumination emergency power. Repair or replace the emergency lighting unit located in the speaker room on the ceiling.
05/08/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.5- illumination emergency power. Test all emergency lighting units and exit signs for emergency back-up power. Replace or repair defective units.
05/08/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.5- illumination emergency power. The exit sign and emergency lighting unit located in the north exit corridor shall have emergency back-up power.
05/08/2008 VIOL - COMPRESSED GASES JBURGE Correction Required TFC 3003.5.3- Securing compressed gas containers, cylinders and tanks. Secure all compressed gas cylinders located in the stock room.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR01162
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
06/04/2008 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.