Inspection History: VIOL - FIRE PROTECTION SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/05/2008 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | Spare head box requires an additional 1/2" brass, 200 degree, upright sprinkler head. cords and wires shall not be hung from sprinkler piping Insulation shall not impede the spray pattern of sprinklers All escutchions that are missing shall be replaced A hydraulic calculation plate shall be at the riser Fire extinguishers shall be serviced on an annual basis |