Case Details

Status:

FIELD

Type:

INSPECTION

Entered Date:

05/05/2008

Applicant:

HEMISPHERE LOOP LLC

Description:

annual inspection

Outstanding Inspections

Case Number: T08FR01102
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
05/05/2008 INSP - REINSPECTION EDESCHAI Continued Reinspection Date 6-5-2008
05/05/2008 VIOL - FIRE PROTECTION SYSTEMS EDESCHAI Correction Required Spare head box requires an additional 1/2" brass, 200 degree, upright sprinkler head. cords and wires shall not be hung from sprinkler piping Insulation shall not impede the spray pattern of sprinklers All escutchions that are missing shall be replaced A hydraulic calculation plate shall be at the riser Fire extinguishers shall be serviced on an annual basis

Completed Inspections

Case Status: FIELD
Case Number: T08FR01102
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
06/27/2008 INSP - FULL EDESCHAI Approved