Case: T08FR01102
Case Details
Entered Date:
05/05/2008
Applicant:
HEMISPHERE LOOP LLC
Description:
annual inspection
Outstanding Inspections
Case Number: T08FR01102
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/05/2008 | INSP - REINSPECTION | EDESCHAI | Continued | Reinspection Date 6-5-2008 |
| 05/05/2008 | VIOL - FIRE PROTECTION SYSTEMS | EDESCHAI | Correction Required | Spare head box requires an additional 1/2" brass, 200 degree, upright sprinkler head. cords and wires shall not be hung from sprinkler piping Insulation shall not impede the spray pattern of sprinklers All escutchions that are missing shall be replaced A hydraulic calculation plate shall be at the riser Fire extinguishers shall be serviced on an annual basis |
Completed Inspections
Case Status: FIELD
Case Number: T08FR01102
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/27/2008 | INSP - FULL | EDESCHAI | Approved |