Case: T08FR00955

Parcel: 126122660


Addresses:

4625 E BROADWAY BL

Inspection Status: Correction Required

Inspection History: VIOL - INT.FINISH, DEC. MATL'S

Date Description Inspector Results Comments
04/15/2008 VIOL - INT.FINISH, DEC. MATL'S Correction Required 803.1.1/803.1.2 Interior finish materials (palm fronds and decorative wall coverings) shall be in accordance with ASTM E 84 class A flame spread for exit passageways and corridors and class B for rooms, or be tested and meet the criteria for interior finish materials tested to NFPA 286. Documentation shall be provided to show that the interior finish materials meet this criteria.