Case Number: T08FR00955
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 14
End Date Description Inspector Results Comments
04/15/2008 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 305.1 The light fixture located in the walk in cooler shall be mounted in such a way as to not cause a hazard. The light shall not be allowed to contact combustibles.
04/15/2008 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 603.5.2 The gas piping for the water heater located in the north side water heater room shall be secured.
04/15/2008 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.1 The light fixture located in the north side water heater room shall be repaired to cover the exposed wiring splice. Splice shall be located within an approved junction box.
04/15/2008 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.5 Extension cords shall not be used as a subsitute for permanent wiring. Cords located in lizard cage. Cords throughout used for lighting.
04/15/2008 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.6 The electrical switch box located near the kitchen restroom shall have an approved cover.
04/15/2008 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.6 The light fixture located in the kitchen above the cooking equipment shall have an approved cover to cover exposed wiring.
04/15/2008 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.6 The open wiring splices located in the west dining area at the celing are prohibited. Splices shall be in approved junction boxes.
04/15/2008 VIOL - INT.FINISH, DEC. MATL'S TKNAPP Correction Required 803.1.1/803.1.2 Interior finish materials (palm fronds and decorative wall coverings) shall be in accordance with ASTM E 84 class A flame spread for exit passageways and corridors and class B for rooms, or be tested and meet the criteria for interior finish materials tested to NFPA 286. Documentation shall be provided to show that the interior finish materials meet this criteria.
04/15/2008 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 901.6 The portable fire extinguisher located in the kitchen shall be inspected annually.
04/15/2008 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 904.11.6.4 The comercial cooking hood system shall be serviced at least every six months.
04/15/2008 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1008.1.2 The exit door located at the west side of the dining area shall open with a force no greater than 15 pounds.
04/15/2008 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1008.1.8.4 The slide bolt lock located on the southwest exit door shall be removed.
04/15/2008 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1027.20 A clear aisle shall be provided in the west dining area to provide access to the northwest exit door. Aisle shall be maintained at least 36 inches in width.
04/15/2008 VIOL - COMPRESSED GASES TKNAPP Correction Required 3003.5.3 The CO2 cylinders located behind the bar shall be secured to prevent them from falling.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR00955
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
06/01/2009 INSP - FULL TKNAPP Approved