Case: T08FR00955
Case Details
Entered Date:
04/15/2008
Applicant:
CLARK PAUL
Description:
Full Inspection
Outstanding Inspections
Case Number: T08FR00955
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 14
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/15/2008 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 305.1 The light fixture located in the walk in cooler shall be mounted in such a way as to not cause a hazard. The light shall not be allowed to contact combustibles. |
| 04/15/2008 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 603.5.2 The gas piping for the water heater located in the north side water heater room shall be secured. |
| 04/15/2008 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.1 The light fixture located in the north side water heater room shall be repaired to cover the exposed wiring splice. Splice shall be located within an approved junction box. |
| 04/15/2008 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.5 Extension cords shall not be used as a subsitute for permanent wiring. Cords located in lizard cage. Cords throughout used for lighting. |
| 04/15/2008 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.6 The electrical switch box located near the kitchen restroom shall have an approved cover. |
| 04/15/2008 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.6 The light fixture located in the kitchen above the cooking equipment shall have an approved cover to cover exposed wiring. |
| 04/15/2008 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.6 The open wiring splices located in the west dining area at the celing are prohibited. Splices shall be in approved junction boxes. |
| 04/15/2008 | VIOL - INT.FINISH, DEC. MATL'S | TKNAPP | Correction Required | 803.1.1/803.1.2 Interior finish materials (palm fronds and decorative wall coverings) shall be in accordance with ASTM E 84 class A flame spread for exit passageways and corridors and class B for rooms, or be tested and meet the criteria for interior finish materials tested to NFPA 286. Documentation shall be provided to show that the interior finish materials meet this criteria. |
| 04/15/2008 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 901.6 The portable fire extinguisher located in the kitchen shall be inspected annually. |
| 04/15/2008 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 904.11.6.4 The comercial cooking hood system shall be serviced at least every six months. |
| 04/15/2008 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1008.1.2 The exit door located at the west side of the dining area shall open with a force no greater than 15 pounds. |
| 04/15/2008 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1008.1.8.4 The slide bolt lock located on the southwest exit door shall be removed. |
| 04/15/2008 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027.20 A clear aisle shall be provided in the west dining area to provide access to the northwest exit door. Aisle shall be maintained at least 36 inches in width. |
| 04/15/2008 | VIOL - COMPRESSED GASES | TKNAPP | Correction Required | 3003.5.3 The CO2 cylinders located behind the bar shall be secured to prevent them from falling. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR00955
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/01/2009 | INSP - FULL | TKNAPP | Approved |