Case: T08FR00905

Parcel: 13409013B


Addresses:

550 S CAMINO SECO


Inspection Status: Correction Required

Inspection History: INSP - REINSPECTION

Case Number - T08FR00905

Inspection Description - INSP - REINSPECTION

Inspection Status - Correction Required

Date Description Inspector Results Comments
04/07/2009 INSP - REINSPECTION Correction Required REINSPECTION:

The Tucson Fire Department has been conducting periodic fire safety re-inspections while this building has undergone extensive renovation. Below are some violations of the Tucson Fire Code ( 2006 International Fire Code with modifications) that shall be corrected in order to come into compliance.

BUILDING 1

___1.PROBLEM: Fire door near unit 1310 not closing properly.
TFC REFERENCE: 703.2.3 Door operation. Swinging fire doors shall close from the full-open position and latch automatically. The door closer shall exert enough force to close and latch the door from any partially open position.
REQUIRED CORRECTION: Fire doors shall function properly.

___2.PROBLEM: Fire door near unit 1207 not closing properly.
TFC REFERENCE: 703.2.3 Door operation. Swinging fire doors shall close from the full-open position and latch automatically. The door closer shall exert enough force to close and latch the door from any partially open position.
REQUIRED CORRECTION: Fire doors shall function properly.

BUILDING 2

___1.PROBLEM: Fire door near unit P232 not closing properly.
TFC REFERENCE: 703.2.3 Door operation. Swinging fire doors shall close from the full-open position and latch automatically. The door closer shall exert enough force to close and latch the door from any partially open position.
REQUIRED CORRECTION: Fire doors shall function properly.

___2.PROBLEM: Fire door 2nd floor middle of hall not closing properly.
TFC REFERENCE: 703.2.3 Door operation. Swinging fire doors shall close from the full-open position and latch automatically. The door closer shall exert enough force to close and latch the door from any partially open position.
REQUIRED CORRECTION: Fire doors shall function properly.

___3.PROBLEM: Fire door at 3rd floor South Exit not closing properly.
TFC REFERENCE: 703.2.3 Door operation. Swinging fire doors shall close from the full-open position and latch automatically. The door closer shall exert enough force to close and latch the door from any partially open position.
REQUIRED CORRECTION: Fire doors shall function properly.

___4.PROBLEM: Fire door at ground floor South exit not closing properly.
TFC REFERENCE: 703.2.3 Door operation. Swinging fire doors shall close from the full-open position and latch automatically. The door closer shall exert enough force to close and latch the door from any partially open position.
REQUIRED CORRECTION: Fire doors shall function properly.

___5.PROBLEM There is a large gap between bottom of door and floor.
TFC-REFERENCE: 703.1 he required fire-resistance rating of fire resistance-rated construction shall be maintained.
REQUIRED CORRECTION: Install door sweep to maintain fire resistive rating.

BUILDING 3

___1.PROBLEM: There is a large gap between bottom of door and floor.
TFC-REFERENCE: 703.1 The required fire-resistance rating of fire resistance-rated construction shall be maintained.
REQUIRED CORRECTION: Install door sweep to maintain fire resistive rating

___2.PROBLEM: The fire door on the third floor in the middle of the hall is being propped open by residents.
TFC-REFERENCE: 703.2.1 Where required by the fire code official, a sign shall be permanently displayed on or near each fire door in letters not less than 1 inch high to read as follows: FIRE DOOR-DO NOT BLOCK.
REQUIRED CORRECTION: You will post the above sign on that door on both sides.

___3.PROBLEM: Your emergency lighting is not working properly.
TFC-REFERENCE: 1106.1 The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied.
REQUIRED CORRECTION: Cause your emergency lights to operate properly.

BUILDING 4

___1.PROBLEM: Fire door on third floor North exit has a broken hinge and not closing properly.
TFC REFERENCE: 703.2.3 Door operation. Swinging fire doors shall close from the full-open position and latch automatically. The door closer shall exert enough force to close and latch the door from any partially open position.
REQUIRED CORRECTION: Fire doors shall function properly.

___2.PROBLEM: Fire door on second floor North exit not closing properly.
TFC REFERENCE: 703.2.3 Door operation. Swinging fire doors shall close from the full-open position and latch automatically. The door closer shall exert enough force to close and latch the door from any partially open position.
REQUIRED CORRECTION: Fire doors shall function properly.

___3.PROBLEM: Fire door on second floor middle of hall not closing properly.
TFC REFERENCE: 703.2.3 Door operation. Swinging fire doors shall close from the full-open position and latch automatically. The door closer shall exert enough force to close and latch the door from any partially open position.
REQUIRED CORRECTION: Fire doors shall function properly.

___4.PROBLEM: There is a large gap between floor and bottom of the fire door.
TFC-REFERENCE: 703.1 The required fire-resistance rating of fire resistance-rated construction shall be maintained.
REQUIRED CORRECTION: Install door sweep to maintain fire resistive rating

___5.PROBLEM: There are two open wiring splices on second floor balcony on South side.
TFC REFERENCE: 605.6 Open junction boxes and open wiring splices are prohibited.
REQUIRED CORRECTION: Place an approved cover over open jbox and wiring splices.

The Tucson Fire Department is committed to the protection of your property and your life safety.Your help as a business owner and as a citizen is greatly appreciated.

Property Representative Signature: _________________________.

Fire Inspector Signature: _________________________(791-4502).

Reinspection Date: ___/___/___ or later.

___Approved

___Not Approved