Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T08FR00905

Parcel: 13409013B


Addresses:

550 S CAMINO SECO


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T08FR00905

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
08/18/2009 INSP - FULL Approved All violations have been corrected.
12/09/2008 INSP - FULL Violation
08/05/2008 INSP - FULL Correction Required 8/05: Met with Steve Heimuli and Inspector Nicole Springer. Reviewed progress on renovations and violations. Inspector Springer to assume this case.
07/07/2008 INSP - FULL Correction Required On 7/3 met with manager Brandi. Renovation activities continue. No recent false alarms reported.Will continue to follow progress of total renovation.
05/30/2008 INSP - FULL Correction Required 5/30/08: stopped by and spoke with Brandi regarding progress of renovations and fire code issues. Brandi states that they will be replacing all smoke detectors in the hallways that are connected to the fire alarm system. Extensive renovation operations are ongoing. Will check on progress in 2 to 3 weeks.
05/15/2008 INSP - FULL Correction Required 05/15/08: Spoke with Steve Heimuli, Brandi, Capt. Tracey regarding the fire alarm situation. Chief Uthe is in agreement that alarm system may be turned off in zones where workers are working to prevent false alarms. Brandi the manager has agreed to keep and document fire watch during those times and to turn the system back on when the workers are finished.
05/13/2008 INSP - FULL Correction Required 05/13/08: Spoke with manager Brandi regarding 2 false alarms yesterday. The first was preventable as workers were not protecting smoke detectors as instructed during renovation. No clear cause of 2nd alarm. Steve Heimuli is scheduled to meet with Central Alarm and discuss options as system is old and will need eventual upgrading.
05/06/2008 INSP - FULL Correction Required 5/6/08: Checked on progress of violation abatements as they are in the process of renovations. Item number 2 under LAUNDRY and 1 under OFFICE abated. Will continue to check on progress.
04/23/2008 INSP - FULL Correction Required 04/23/08: Spoke with manager Brandi Young, Steve Heimuli and Central Alarm. Have had recent false alarms related to extensive renovation activity. Ascertained that only the heat detectors in the rooms and the heat detectors in the hallways and the smoke detectors in the hallways are wired into the fire alarm system. The smoke detectors in the units are not wired into the fire alarm system. Will allow work crews to cover the hallway smoke detectors while they are present and working. When they leave the work area they must uncover the smoke detectors. The manager Brandi has agreed to double check when the workers leave and confirm that the covers have been removed.
04/09/2008 INSP - FULL Correction Required The Tucson Fire Department has conducted a fire safety inspection at the above stated business . Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2006 International Fire Code (with modifications).

BUILDING 1

___1. PROBLEM: Fire door near units 1207 and 1208 do not close properly.
TFC REFERENCE: 703.2.3 Door operation. Swinging fire doors shall close from the full-open position and latch automatically. The
door closer shall exert enough force to close and latch the
door from any partially open position.
REQUIRED CORRECTION: Fire doors shall function properly.

___2. PROBLEM: Emrgency lights above fire door by units 1216 and 1316 do not function properly.
TFC REFERENCE: 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied.
REQUIRED CORRECTION: Emergency lighting units shall be functioning properly.

___3. PROBLEM: Open light socket above door leading to 1300 units.
TFC REFERENCE: 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
REQUIRED CORRECTION: All light fixtures shall have proper bulbs and covers.

BUILDING 2

___1. PROBLEM: Outside fire door on 2nd floor does not close properly.
TFC REFERENCE: See above
REQUIRED CORRECTION: See above.

___2. PROBLEM: Open light socket above door on 2nd floor.
TFC REFERENCE: See above
REQUIRED CORRECTION: See above.

BUILDING 3

___1. PROBLEM: Outside fire door on 1st floor has damaged self closing hardware.
TFC REFERENCE: 703.2.3 Door operation. Swinging fire doors shall close from the full-open position and latch automatically. The
door closer shall exert enough force to close and latch the
door from any partially open position.
REQUIRED CORRECTION: Self closing hardware shall function properly in accordance with code requirements.

___2. PROBLEM: Damaged fire door on outside first floor.
TFC REFERENCE:703.2 Opening protectives. Opening protectives shall be maintained in an operative condition in accordance with NFPA 80. Fire doors and smoke barrier doors shall not be blocked or
obstructed or otherwise made inoperable.
REQUIRED CORRECTION: Fire doors shall maintain their fire rating and shall not have damage that would diminish such.

BUILDING 4

___1. PROBLEM: Outside fire door on 2nd floor is damaged and will not close properly.
TFC REFERENCE: See above.
REQUIRED CORRECTION: See above.

___2. PROBLEM: Damaged exit sign on 1st floor leading outside.
TFC REFERENCE:1011.4 Internally illuminated exit signs. Internally illuminated exit signs shall be listed and labeled and shall be installed in accordance with the manufacturer’s instructions and Section 2702 of the International Building Code. Exit signs shall be
illuminated at all times.
REQUIRED CORRECTION: Exit signs shall not be in a state of disrepair and shall function properly.

LAUNDRY ROOM

___PROBLEM: Lint build up behind dryers.
TFC REFERENCE: Section 316.2 Clothes dryers.(cot mod) Clothes dryers shall be frequently cleaned to maintain the lint trap and mechanical and heating components free from excessive accumulations of lint.
REQUIRED CORRECTION: Keep area behind dryers free of lint and combustible wastes.

___2. PROBLEM: Outside light by pop machine needs cover.
TFC REFERENCE: 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of
the code official responsible for enforcement of the ICC Electrical
Code. Electrical wiring, devices, appliances and other
equipment that is modified or damaged and constitutes an electrical
shock or fire hazard shall not be used.
REQUIRED CORRECTION: Have proper cover placed on light fixture.

POOL AREA

___1. PROBLEM: Pool chemicals stored outside uncovered and exposed to the elements.
TFC REFERENCE: 2701.3.3.6 Protection of hazardous materials. Safeguards shall be provided to minimize the risk of exposing hazardous materials to a fire or physical damage whereby such exposure could endanger or lead to the endangerment of people or property.
REQUIRED CORRECTION: Pool chemicals shall be safely stored in a room or shed and not exposed to the elements or heat.

OFFICE AREA

___1. PROBLEM: Open light fixture with exposed wire by office entrance.
TFC REFERENCE: 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
REQUIRED CORRECTION: Exposed wiring shall be properly covered.

___2. PROBLEM: Open junction boxes in rec. hall on ceiling.
TFC REFERENCE: 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
REQUIRED CORRECTION: Junction boxes shall be covered with approved fixture or cover.

___3. PROBLEM: Fire extinguisher in rec. hall lacking service tag.
TFC REFERENCE: 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an
operative condition at all times, and shall be replaced or
repaired where defective. Nonrequired fire protection systems
and equipment shall be inspected, tested and maintained or
removed.
REQUIRED CORRECTION: All fire extinguishers must be service yearly or removed from premises.

___4. PROBLEM: Smoke detector not working in one of the empty units.
TFC REFERENCE: 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an
operative condition at all times, and shall be replaced or
repaired where defective.
REQUIRED CORRECTION: Smoke detectors shall be in operative condition at all times.

The Tucson Fire Department is committed to the protection of your property and your life safety.Your help as a business owner and as a citizen is greatly appreciated.

Property Representative Signature: _________________________.

Fire Inspector Signature: _________________________(791-4502).

Reinspection Date: ___/___/___ or later.

___Approved

___Not Approved