Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T08FR00856
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/15/2008 | VIOL - BUILDING SVCS & SYSTEMS | Approved | ||
04/08/2008 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 2006 IFC 605.4 REMOVE MULTIPLUG ADAPTER IN PRODUCE BY SINK AND REPLACE WITH A FUSED POWER STRIP |
|
04/08/2008 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 2006 IFC 605.5 REMOVE EXTENSION CORD USED ON MEAT GRINDER AND USE A FUSED POWER STRIP. |
|
04/08/2008 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 2006 IFC 605.5 REMOVE EXTENSION CORD IN BAKERY BACK ROOM BY SINK. |
|
04/08/2008 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 2006 IFC 605.5 REMOVE EXTENSION CORD BY COFFE DISPLAY BY MEAT DEPT. |
|
04/08/2008 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 2006 IFC 605.1 REPLACE MISSING COVER PLATE ON OUTLET IN DELI BY THE DELI CASE. |
|
04/08/2008 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 2006 IFC 605.5 REMOVE EXTENSION CORD BY COFFEE MACHINES UNDER NEATH THE COUNTER. |