Case: T08FR00802

Parcel: 115051500


Addresses:

2226 N STONE AV


Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T08FR00802

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Correction Required

Date Description Inspector Results Comments
03/27/2008 VIOL - MEANS OF EGRESS Correction Required 1008.1.8.5 Unlatching.
The unlatching of any door or leaf shall not require more than one operation.

_____ Remove key turn bolt lock from main entrance door

1008.1.8.3 Locks and latches.
Locks and latches shall be permitted to prevent operation of doors where any of the following exists…
-- 2. In buildings in occupancy Group A having an occupant load of 300 or less, Groups B, F, M and S, and in places of religious worship, the main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress
side provided:
-- 2.1. The locking device is readily distinguishable as locked,
-- 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background, -- 2.3. The use of the key-operated locking device is revokable by the fire code official for due cause.

_____ Properly label "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED" above main entrance door