Case: T08FR00492

Parcel: 11618432G

Inspection Status: Correction Required

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
02/15/2008 VIOL - BUILDING SVCS & SYSTEMS Correction Required TFC 605.1 Abatement of electrical hazards. Repair the leaks in the roof so water cannot flow into the electrical service equipment.
02/15/2008 VIOL - BUILDING SVCS & SYSTEMS Correction Required TFC 605.6- Provide blanks for all open spaces in the electrical panels.
02/15/2008 VIOL - BUILDING SVCS & SYSTEMS Correction Required TFC 605.3 No storage of any materials shall be located within 36 inches of electrical service equipment.
02/15/2008 VIOL - BUILDING SVCS & SYSTEMS Correction Required TFC 605.1- Remove all moisture from the electrical service panels and have all electrical systems checked by an electrical contractor.