Case Details

Status:

COMPLETE

Type:

COMPLAINT (COMMERCIAL)

Entered Date:

02/15/2008

Applicant:

MENLO PARK SHOPPING CENTER COMPANY

Description:

Called out by Medic 1 for electrical hazards.

Outstanding Inspections

Case Number: T08FR00492
Case Status: COMPLETE
Case Description: COMPLAINT (COMMERCIAL)
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
02/15/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.1 Abatement of electrical hazards. Repair the leaks in the roof so water cannot flow into the electrical service equipment.
02/15/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.1- Remove all moisture from the electrical service panels and have all electrical systems checked by an electrical contractor.
02/15/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.3 No storage of any materials shall be located within 36 inches of electrical service equipment.
02/15/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.6- Provide blanks for all open spaces in the electrical panels.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR00492
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 1
End Date Description Inspector Results Comments
02/29/2008 INSP - LIFE SAFETY JBURGE Approved All noted Tucson Fire Code violations were corrected.