Inspection Status: Correction Required
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
| Date |
Description |
Inspector |
Results |
Comments |
| 02/15/2008 |
VIOL - FIRE PROTECTION SYSTEMS |
|
Correction Required |
TFC 906.6 The portable fire extinguisher located by the main entrance shall not be obstructed or obscured. |
| 02/15/2008 |
VIOL - FIRE PROTECTION SYSTEMS |
|
Correction Required |
TFC 906.9 The portable fire extinguisher located by the main entrance shall be mounted so that it's top is no more than 5 ft above the floor. |
| 02/15/2008 |
VIOL - FIRE PROTECTION SYSTEMS |
|
Correction Required |
TFC 901.6 Repair or replace the water flow gong for the automatic sprinkler system located on the southwest side of the building. |