Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

02/15/2008

Applicant:

CENTRO NP HOLDINGS 1 SPE LLC

Description:

Full Inspection.

Outstanding Inspections

Case Number: T08FR00489
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date Description Inspector Results Comments
02/15/2008 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC 505.1 Address numbers shall be in accordance with Pima County address display requirements.
02/15/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.3 Remove the storage from obstructing the electrical service equipment located by the employee break room.
02/15/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 Repair or replace the water flow gong for the automatic sprinkler system located on the southwest side of the building.
02/15/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 906.6 The portable fire extinguisher located by the main entrance shall not be obstructed or obscured.
02/15/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 906.9 The portable fire extinguisher located by the main entrance shall be mounted so that it's top is no more than 5 ft above the floor.
02/15/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8.3-2.2 Post a sign above the inside of the main entrance doors stating," THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED."
02/15/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.4 The exit sign located by the restrooms shall be illuminated during power supply failure.
02/15/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.5 Test and repair all emergency lighting units that do not operate during power supply failure.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR00489
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
06/03/2008 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.