Case: T08FR00372

Parcel: 141148150

Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T08FR00372

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
02/26/2008 INSP - FULL Approved
02/05/2008 INSP - FULL Correction Required The Tucson Fire Department has conducted a fire safety inspection at the above stated business . Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2006 International Fire Code (with modifications).

___1. PROBLEM: Cube adapters used up front and by radio.
TFC REFERENCE: 605.4 Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited.
REQUIRED CORRECTION: Remove power strips and plug appliances directly into outlet or into approved power strip. Power strip must be plugged directly into outlet.

___2. PROBLEM: Orange extension cord used for refridgerator and microwave and yellow extension cord used as wiring running up wall.
TFC REFERENCE: 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage
or physical impact. Extension cords shall be used only with
portable appliances.
REQUIRED CORRECTION: Plug appliances into electrical outlet or may use power strip.

___3. PROBLEM: Hole in wall above restroom.
TFC REFERENCE: 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops,
shaft enclosures, partitions, smoke barriers, floors, fire-resistive
coatings and sprayed fire-resistant materials applied to
structural members and fire-resistant joint systems) shall be
maintained. Such elements shall be properly repaired, restored
or replaced when damaged, altered, breached or penetrated.
Openings made therein for the passage of pipes, electrical conduit,
wires, ducts, air transfer openings and holes made for any
reason shall be protected with approved methods capable of
resisting the passage of smoke and fire.
REQUIRED CORRECTION: Hole in wall must be repaired with proper fire rated materials.

The Tucson Fire Department is committed to the protection of your property and your life safety. Your help as a business owner and as a citizen is greatly appreciated.

Property Representative Signature: _________________________.

Fire Inspector Signature: _________________________(791-4502).

Reinspection Date: ___/___/___ or later.

__X_Approved

___Not Approved