Case: T08FR00318

Parcel: 141148150

Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T08FR00318

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
02/04/2008 INSP - FULL Approved
01/31/2008 INSP - FULL Correction Required The Tucson Fire Department has conducted a fire safety inspection at the above stated business . Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2006 International Fire Code (with modifications).

___1. PROBLEM: Cube adapter used in office.
TFC REFERENCE: 605.4 Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited.
REQUIRED CORRECTION: Plug appliances directly into outlet or use a power strip.

___2. PROBLEM: Cover plate missing from hole in wall for outlet.
TFC REFERENCE: 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. ALSO SEE: 703.1 Maintenance. The required fire-resistance rating of
fire-resistance-rated construction (including walls, firestops,
shaft enclosures, partitions, smoke barriers, floors, fire-resistive
coatings and sprayed fire-resistant materials applied to
structural members and fire-resistant joint systems) shall be
maintained. Such elements shall be properly repaired, restored
or replaced when damaged, altered, breached or penetrated.
REQUIRED CORRECTION: Approved cover plate shall be secured to open box in wall.

The Tucson Fire Department is committed to the protection of your property and your life safety. Your help as a business owner and as a citizen is greatly appreciated.

Property Representative Signature: _________________________.

Fire Inspector Signature: _________________________(791-4502).

Reinspection Date: ___/___/___ or later.

_X__Approved

___Not Approved