Case: T08FR00303

Parcel: 141148150

Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T08FR00303

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
03/13/2008 INSP - FULL Approved Spoke with Rachel from Venture West the property manager. She stated that they would check and replace all missing escutcheon plates in the complex.
03/05/2008 INSP - FULL Correction Required Needs time for sprinkler co. to fix
01/28/2008 INSP - FULL Correction Required The Tucson Fire Department has conducted a fire safety inspection at the above stated business . Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2006 International Fire Code (with modifications).

___1. PROBLEM: Emergency lighting at front exit not functioning.
TFC REFERENCE: 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an
operative condition at all times, and shall be replaced or
repaired where defective. AND: 1011.2 Illumination. Exit signs shall be internally or externally illuminated.
REQUIRED CORRECTION: Have all emergency lighting checked and repaired where necessary.

___2. PROBLEM: Sprinkler head missing escutcheon plate in back office and in restroom.
TFC REFERENCE: 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an
operative condition at all times, and shall be replaced or
repaired where defective.
REQUIRED CORRECTION: Have missing escutcheon plates replaced on sprinkler heads.

___3. PROBLEM: Electrical panels blocked in back office.
TFC REFERENCE: 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in
front of electrical service equipment. Where the electrical service
equipment is wider than 30 inches (762 mm), the working
space shall not be less than the width of the equipment. No storage
of any materials shall be located within the designated
working space.
REQUIRED CORRECTION: Provide proper clearance around electrical panels.

___4.PROBLEM: Sprinkler system riser room needs a durable sign designating it as such.
TFC REFERENCE: 510.1 Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required
to identify fire protection equipment and equipment location,
shall be constructed of durable materials, permanently
installed and readily visible.
REQUIRED CORRECTION: Have sign affixed to sprinkler system riser room.


The Tucson Fire Department is committed to the protection of your property and your life safety. Your help as a business owner and as a citizen is greatly appreciated.

Property Representative Signature: _________________________.

Fire Inspector Signature: _________________________(791-4502).

Reinspection Date: ___/___/___ or later.

_X__Approved

___Not Approved