Case: T08FR00302

Parcel: 141148180

Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T08FR00302

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
02/14/2008 INSP - FULL Approved
01/28/2008 INSP - FULL Correction Required The Tucson Fire Department has conducted a fire safety inspection at the above stated business . Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2006 International Fire Code (with modifications).

___1. PROBLEM: Open blank in electrical panel.
TFC REFERENCE: 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated.
REQUIRED CORRECTION: Add a blank tab to open space in electrical panel.

___2. PROBLEM: Some red caps are missing from hood suppression system nozzles.
TFC REFERENCE: 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an
operative condition at all times, and shall be replaced or
repaired where defective. AND NFPA 17A 4.3.1.5: NFPA 17A, 4.3.1.5: All discharge nozzles shall be provided with caps or other suitable devices to prevent the entrance of grease vapors, moisture or other foreign materials into the piping.
REQUIRED CORRECTION: Replace caps on nozzle tips.

The Tucson Fire Department is committed to the protection of your property and your life safety. Your help as a business owner and as a citizen is greatly appreciated.

Property Representative Signature: _________________________.

Fire Inspector Signature: _________________________(791-4502).

Reinspection Date: ___/___/___ or later.

__X_Approved

___Not Approved