Case: T08FR00239

Parcel: 141148180

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
02/19/2008 INSP - FULL Approved Reinspection on 2/19/08 shows all violations corrected.
01/24/2008 INSP - FULL Correction Required The Tucson Fire Department has conducted a fire safety inspection at the above stated business . Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2006 International Fire Code (with modifications).

___1. PROBLEM: Hole in ceiling tile compromising fire rated construction.
TFC REFERENCE: 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops,
shaft enclosures, partitions, smoke barriers, floors, fire-resistive
coatings and sprayed fire-resistant materials applied to
structural members and fire-resistant joint systems) shall be
maintained. Such elements shall be properly repaired, restored
or replaced when damaged, altered, breached or penetrated.
REQUIRED CORRECTION: Replace ceiling tile.

___2. PROBLEM: Power strip piggy backed into power strip above restroom.
TFC REFERENCE: 605.4.2 Power supply. Relocatable power taps shall be directly connected to a permanently installed receptacle.
REQUIRED CORRECTION: Plug power strip directly into electrical outlet.

The Tucson Fire Department is committed to the protection of your property and your life safety. Your help as a business owner and as a citizen is greatly appreciated.

Property Representative Signature: _________________________.

Fire Inspector Signature: _________________________(791-4502).

Reinspection Date: ___/___/___ or later.