Case: T08FR00224

Parcel: 141153560


Addresses:

8150 S HOUGHTON RD


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T08FR00224

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
02/07/2008 INSP - FULL Approved
01/22/2008 INSP - FULL Correction Required The Tucson Fire Department has conducted a fire safety inspection at the above stated business . Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2006 International Fire Code (with modifications).

___1. PROBLEM: Power strips under desks are not secured
TFC REFERENCE: 605.4.3 Installation. Relocatable power tap cords shall not extend through walls, ceilings, floors, under doors or floor
coverings, or be subject to environmental or physical damage.
REQUIRED CORRECTION: Properly secure power strips so as to prevent damage to plugs or power strip.

___2. PROBLEM: Sprinkler riser room needs sign to identify it as such.
TFC REFERENCE: 510.1 Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required
to identify fire protection equipment and equipment location,
shall be constructed of durable materials, permanently installed and readily visible.
REQUIRED CORRECTION: Have permanent sign affixed to outside of sprinkler riser room identifying it as such

___3. PROBLEM: Sprinkler head in water heater closet has cables resting on it. This can affect the sprinkler pattern/coverage
TFC REFERENCE: 903.3.3 Obstructed locations. Automatic sprinklers shall be installed with due regard to obstructions that will delay activation or obstruct the water distribution pattern.
REQUIRED CORRECTION: Move cables so they are not in way of spray pattern. Do not secure cables to sprinkler piping.



RECOMMENDATION: Install a lock box (Knox Box) next to sprinkler riser room with key to sprinkler room inside. This makes access by the Fire Dept. quicker so system can be accessed in the event it is activated. This is NOT a requirement, merely a recommendation.

The Tucson Fire Department is committed to the protection of your property and your life safety. Your help as a business owner and as a citizen is greatly appreciated.


Property Representative Signature: _________________________.

Fire Inspector Signature: _________________________(791-4502).

Reinspection Date: ___/___/___ or later.

_X__Approved

___Not Approved