Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/26/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/15/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*' 1. MUST HAVE 36" OF CLEAR SPACE IN FRONT OF SUB-PANEL 2. FLEX CONDUIT NOT SUPPORTED 3. CIRCUIT BREAKERS MUST BE SAME BRAND AS PANEL, INSTALL GROUND TERMINAL BAR IN PANEL 4. EXPOSED ROMEX ON SOUTH SIDE OF M.H. 5. OK COOLER HOOK UP 6. NO DOUBLE LUGGING ON MAIN BREAKER - WIRE SIZE TO SMALL FOR 60A BREAKER WHERE DOES SUB-PANEL GET ITS FEED FROM? |