Permit: T08EL02320

Parcel: 10321025C

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08EL02320

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/26/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/15/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*'
1. MUST HAVE 36" OF CLEAR SPACE IN FRONT OF SUB-PANEL
2. FLEX CONDUIT NOT SUPPORTED
3. CIRCUIT BREAKERS MUST BE SAME BRAND AS PANEL, INSTALL GROUND TERMINAL BAR IN PANEL
4. EXPOSED ROMEX ON SOUTH SIDE OF M.H.
5. OK COOLER HOOK UP
6. NO DOUBLE LUGGING ON MAIN BREAKER - WIRE SIZE TO SMALL FOR 60A BREAKER

WHERE DOES SUB-PANEL GET ITS FEED FROM?