Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/21/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/16/2008 | ELECTRIC - FINAL | Denied | - OLD RESIDENCE GOING TO BE GRANITE COUNTERTOP COMPANY OUTSIDE: 1. CAP WIRES AND COVER BOXES EXPOSED CONDUCTORS 2. PROPERLY ATTACH FIXTURE TO BOX 3. SUPPORT BOXES & CONDUIT TO STRUCTURE 4. BOXES TO BE FOR WET LOCATION & COVERS 5. SECURE GROUNDING ELECTRODE CONDUCTOR TO STRUCTURE 6. ADDRESS LABEL TO BE PERMANENT 7. PLEASE VERIFY GAS & WATER BONDS INTERIOR: 1. PLEASE VERIFY PERMITS FOR NEW WIRING INSIDE 2. ONLY ONE CONDUCTOR PER TERMINAL SCREW 3. GROUND DEVICES 4. USE APPROVED HARDWARE FOR DEVICES - NOT DRYWALL SCREWS 5. EXPOSED CONDUCTOR & NO BOXES 6. GROUNDED RECEPTACLES ON UNGROUND WIRING 7. BOXES MORE THAN 1/4" FROM BOX TO SURFACE *QUALIFIED ELECTRICIAN MUST DO WORK |