Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/16/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BEDROOMS REQUIRE SMOKIES 2) KITCHEN COUNTER RECEPTACLES MUST BE GFI PROTECTED 3) NEED TO BOND GAS LINE 4) NEED TO USE APPROVED PIPING FOR TPR LINE AT WATER HEATER NOT PVC 5) WILL NEED A SEDIMENT TRAP AT GAS LINE WATER HEATER 6) NEED TO ADD GFI RECEPTACLE AT MASTER BATH FOR DBL LAVS 7) NEED HIGH/LOW COMBUSTION AIR AT WATER HEATER 8) NEED TO REPAIR OUTSIDE GFI RECEPTACLE COVER S.W. CORNER |