Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/16/2008 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 08/26/2008 | ELECTRIC - RECONNECT | Denied | 1) SERVICE PANEL NEEDS TO BE CLEANED UP 2) BREAKERS OVER SIZED FOR WIRE, LABEL CIRCUITS 3) REMOVE WIRING IN GARAGE OR BRING UP TO CODE 4) WIRING ON ROOF TO BE IN RIGID CONDUIT SUPPORTED ON BLOCKS 5) ADDITION ON EAST SIDE TO BE PERMITTED, BUILT WITH PERMIT 6) ADDITION AT REAR PORCH, FAMILY ROOM 7) INSTALL LIGHT FIXTURES OR BLANK OFF 8) SMOKE DETECTOR IN EACH BEDROOM ONE IN HALLWAY 9) GFCI RECEPT AT KITCHEN COUNTER 10) WHERE IS JACUZZI ACCESS PANEL SHOULD BE ON IT'S OWN CIRCUIT |
|
| 08/21/2008 | ELECTRIC - RECONNECT | Not ready for Inspection | IVRS - Inspection :* |