Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08EL01259
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/21/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) TUV FIELD EVALUATION OF SIEMENS SWITCH BOARD 2) RECEIVED CHECK FROM COCHISE ELECTRIC #18425 FOR $150.00 |
|
07/11/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CENTER SWITCH BOARD SECTION WAS REPLACED IN FIELD NEED TO HAVE FIELD EVALUATION DONE ON ENTIRE SWITCHBOARD BY A NATIONALLY RECOGNIZED TESTING LABORATORY 2. NEED TO HAVE ENTIRE SWITCHBOARD OPENED FOR INSPECTION. THIS INCLUDES THE UTILITY SECTION 3. TALKED WITH TODD STOCKSDALE AT TEP, POWER WILL NOT BE SHUT OFF AS LONG AS NRTL IS CONTRACTED TO DO FIELD EVALUATION BY 7/18/08 NEED TO CALL ME RICH JIROUDEK @ 954-0161 AND TODD STOCKSDALE @ 917-8715 BY 7/18/08 TO GIVE US STATUS ON NRTL OR TEP WILL BE SHUTTING OFF POWER |