Permit: T08EL01259

Parcel: 141148150


Addresses:

9050 E VALENCIA RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08EL01259

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/21/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) TUV FIELD EVALUATION OF SIEMENS SWITCH BOARD
2) RECEIVED CHECK FROM COCHISE ELECTRIC #18425 FOR $150.00
07/11/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CENTER SWITCH BOARD SECTION WAS REPLACED IN FIELD
NEED TO HAVE FIELD EVALUATION DONE ON ENTIRE SWITCHBOARD BY A NATIONALLY RECOGNIZED TESTING LABORATORY
2. NEED TO HAVE ENTIRE SWITCHBOARD OPENED FOR INSPECTION. THIS INCLUDES THE UTILITY SECTION
3. TALKED WITH TODD STOCKSDALE AT TEP, POWER WILL NOT BE SHUT OFF AS LONG AS NRTL IS CONTRACTED TO DO FIELD EVALUATION BY 7/18/08

NEED TO CALL ME RICH JIROUDEK @ 954-0161
AND TODD STOCKSDALE @ 917-8715 BY 7/18/08 TO GIVE US
STATUS ON NRTL OR TEP WILL BE SHUTTING OFF POWER