Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08EL00634
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/02/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
04/25/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ALL CORRECTIONS TO BE COMPLETE 2. UNIT TO BE OPEN FOR INSPECTION |
|
04/18/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED SMOKE DETECTOR IN BEDROOM AND HALLWAY MIN. 36" AWAY FROM VENTS, INSTALLED PER MANUFACTURES INSTRUCTIONS 2. ALL BATHROOM AND KITCHEN COUNTER RECEPTACLES TO HAVE GFI PROTECTION 3. INSTALL CONNECTOR FOR DISPOSAL CORD 4. OPEN TYPE BULB FIXTURE NOT ALLOWED IN CLOTHES CLOSET 5. IDENTIFY PANEL DIRECTORY 6. RECEPTACLES TO BE GROUNDED OR BE OF THE NON-GROUNDING TYPE OR GFI PROTECTED 7. REMOVE IMPROPERLY WIRED RECEPTACLE AT EXTERIOR ENTRY OR BRING UP TO CODE |