Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T08EL00318
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/03/2008 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
02/28/2008 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SERVICE CONDUCTORS APPEAR TO HAVE DAMAGED INSULATION 2. BOND ALL STEEL & METAL PIPES TO SERVICE 3. CLAMP FOR GROUND ROD NOT RATED FOR DIRECT BURIAL 4. DRIVE GROUND RODS FLUSH 5. NEED APPROVED LOAD FOR SERVICE TO BE ENERGIZED PERMITS ARE REQUIRED FOR ANY REMODEL/REPAIR WORK 6. LOOP WIRE INTO METER TERMINATIONS |