Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T08EL00318

Parcel: 117041900


Addresses:

127 W 5TH ST


Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T08EL00318

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Approved

Date Description Inspector Results Comments
03/03/2008 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
02/28/2008 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SERVICE CONDUCTORS APPEAR TO HAVE DAMAGED INSULATION
2. BOND ALL STEEL & METAL PIPES TO SERVICE
3. CLAMP FOR GROUND ROD NOT RATED FOR DIRECT BURIAL
4. DRIVE GROUND RODS FLUSH
5. NEED APPROVED LOAD FOR SERVICE TO BE ENERGIZED
PERMITS ARE REQUIRED FOR ANY REMODEL/REPAIR WORK
6. LOOP WIRE INTO METER TERMINATIONS