Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/22/2008 | ELECTRIC - FINAL | Approved | CONTR. REQUESTED AFTER HOURS INSPECTION PAID WITH CHECK #000310 FOR $150.00 | |
| 02/13/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK GROUNDING, CALL FOR INSPECTION WHEN TERMINATION INTO TERM CAN |
|
| 01/31/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* CHASE NIPPLE WITH RE-WASHERS NOT LISTED FOR BONDING AT SERVICES, USE A CLOSE NIPPLE WITH LOCKNUTS (BONDING TYPE) OR BOND BUSHING PER 250.92 NEC THE SAME IS APPLICABLE FOR THE TERMINATION INTO THE GUTTER. |
|
| 01/14/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |