Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/07/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/06/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* SPACE OCCUPIED WITHOUT CLEARANCES NEED CEILING OPENED UP TO INSPECT PANEL NOT AS PER 408.4 |
|
| 01/02/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) BOX OVER FILLED 2) VDV CABLING IN AREA TO BE PER 725.3 & 24, 800.3 & 24 AND 300.11 3) PLANS FOR THIS JOB CALL FOR 3/4" CONDUIT. YOU HAVE 2 CONDUCTOR M/C CABLE 4) RELEASE PANEL PER PLANS AND 408.4 |