Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T08CM03674

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
11/25/2009 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
1) OK FOR CEILING TILES
09/21/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) SUSPENDED ROUGH DUCT OK TO INSULATE
2) SUPPLY AND EXHAUST IN RESTROOMS OK TO COVER
3) CONDENSATE OK
4) CORRECTIONS FROM PREVIOUS INSPECTION OK
5) STILL NEED LETTER FROM ENGINEER
09/10/2009 MECHANICAL - ABOVE CEILING Denied 1. VERIFY BATTERY INSULATION & SOUND BOARD IN ALL RTU CURBS PER DETAIL 11 M2
2, ALL EXHAUST DUCT TO BE RECTANGULAR WITH 1" LINER PER SPECS
3. SEAL ALL DUCT JOINTS
4. DUCT HANGERS NOT TO EXCEED 4"
5. PROVIDE METAL WORMGEAR BANDS (NOT PANDUITS) PER PLANS.
6.SUPPLY DUCT TOO SMALL FOR UNITS, TRANSITION DUCT TO UNIT OPENING. (NO BLANK OFFS) SEE DETAIL 8 M2
7. PROVIDE ENGINEERS WRITTEN APPROVAL ON ANY CHANGES TO PLANS INCLUDING UNIT LOCATION
09/09/2009 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*