Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T08CM03674
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/25/2009 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* 1) OK FOR CEILING TILES |
|
09/21/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) SUSPENDED ROUGH DUCT OK TO INSULATE 2) SUPPLY AND EXHAUST IN RESTROOMS OK TO COVER 3) CONDENSATE OK 4) CORRECTIONS FROM PREVIOUS INSPECTION OK 5) STILL NEED LETTER FROM ENGINEER |
|
09/10/2009 | MECHANICAL - ABOVE CEILING | Denied | 1. VERIFY BATTERY INSULATION & SOUND BOARD IN ALL RTU CURBS PER DETAIL 11 M2 2, ALL EXHAUST DUCT TO BE RECTANGULAR WITH 1" LINER PER SPECS 3. SEAL ALL DUCT JOINTS 4. DUCT HANGERS NOT TO EXCEED 4" 5. PROVIDE METAL WORMGEAR BANDS (NOT PANDUITS) PER PLANS. 6.SUPPLY DUCT TOO SMALL FOR UNITS, TRANSITION DUCT TO UNIT OPENING. (NO BLANK OFFS) SEE DETAIL 8 M2 7. PROVIDE ENGINEERS WRITTEN APPROVAL ON ANY CHANGES TO PLANS INCLUDING UNIT LOCATION |
|
09/09/2009 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |