Permit: T08CM03614

Parcel: 136092090

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM03614

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/11/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/17/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) THIS PANEL NOT LISTED FOR USE WITH SPLIT BREAKERS. SPLIT BREAKERS INSTALLED IN PANEL ARE FOR REPLACEMENT USE ONLY NOT FOR NEW INSTALLS
2) EXPOSE UNDERGROUND CABLING TO POLE, MINIMUM DEPTH TO BE PER NEC 300.5
3) EXPOSE PVC TO BE SCHEDULE 80, STRAP WITHIN 3' OF PANEL CONNECTION
4) CONNECT EQUIPMENT GROUND TO POLE
5) NEED TO VERIFY WATTAGE OF LAMP
6) HEIGHT OF POLE TO BE NO MORE THAN 12' PER PLANS
11/09/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no plan or job inspection card on site.| 925*
1) POST ADDRESS ON HOUSE
2) HAVE APPROVED PLANS AND PERMITS ON SITE
3) ALL NEW WORK TO BE EXPOSED