Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM03439
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/04/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
02/27/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. PREVIOUS INSPECTION ITEMS CORRECTED 2. STILL NEED TO INSPECT CEILINGS WHEN NEW LIGHT FIXTURES INSTALLED THAT WERE NOT SHIPPED ON TIME 3. CHECK WITH BUILDING INSPECTOR FOR TCO I HAVE NO ISSUES. |
|
02/26/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. RECEPTS WITH NO POWER 2. ROOFTOP GFI NO POWER 3. MISSING EM LIGHTS REAR OF BUILDING 4. TERMINATE NEUTRAL FOR X-RAY IN PANEL WITH PROPER LUG 5. NEED PANEL DIRECTORIES 6. WILL HAVE TO DO ANOTHER CEILING INSPECTION AFTER NEW LIGHT FIXTURES INSTALLED THAT DID NOT SHIP ON TIME |