Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/22/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* OK WALLS |
|
| 01/20/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. MC CABLE TO BE PROTECTED FROM PHYSICAL DAMAGE NEED 1 1/4" CLEARANCE TO FACE OF STUD OR PROVIDE PROTECTION 2. STRAP 3/4" EMT WITHIN 12" OF CONNECTIONS 3. I HAVE NO ISSUES WITH ONE SIDING RECALL WHEN ABOVE CORRECTIONS MADE |