Permit: T08CM03439

Parcel: 141148150

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T08CM03439

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
01/22/2009 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
OK WALLS
01/20/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. MC CABLE TO BE PROTECTED FROM PHYSICAL DAMAGE NEED 1 1/4" CLEARANCE TO FACE OF STUD OR PROVIDE PROTECTION
2. STRAP 3/4" EMT WITHIN 12" OF CONNECTIONS
3. I HAVE NO ISSUES WITH ONE SIDING
RECALL WHEN ABOVE CORRECTIONS MADE