Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T08CM03401
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/05/2010 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
02/26/2010 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK FOR CEILING TILES 2ND FLOOR PIMA HEART |
|
02/24/2010 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK FOR CEILING TILES 1ST FLOOR |
|
02/22/2010 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
01/08/2010 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
12/30/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* |