Permit: T08CM03270

Parcel: 12205003C

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/13/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
EXITS AND EE OK
02/04/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
MC CONNECTOR UNDER PANEL 110 REMOVE AND PUT K.O SEAL 4, 5, 6 NOT READY
01/02/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GFI IN BATHROOM DOES NOT WORK
2) NEED APPROVED SPACER FOR LIGHT SWITCH AND NEED ARC SHIELD
3) OUTLET HAS MORE THAN 1/8 CLEARANCE AROUND MUD RING NEX TO FRONT DOOR
4) EXITS AND EM LIGHTS NEED TO BE ON CIRCUIT FOR THAT AREA
5) NEED PANELS LABELED, AND NEED PANEL DIRECTORY FOR PANELS
6) QUAD OUTLET NEXT TO PANEL 110 NEEDS TO BE GFI
7) NEED WORKING CLEARANCE FOR PANELS