Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM03270
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/13/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* EXITS AND EE OK |
|
02/04/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* MC CONNECTOR UNDER PANEL 110 REMOVE AND PUT K.O SEAL 4, 5, 6 NOT READY |
|
01/02/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GFI IN BATHROOM DOES NOT WORK 2) NEED APPROVED SPACER FOR LIGHT SWITCH AND NEED ARC SHIELD 3) OUTLET HAS MORE THAN 1/8 CLEARANCE AROUND MUD RING NEX TO FRONT DOOR 4) EXITS AND EM LIGHTS NEED TO BE ON CIRCUIT FOR THAT AREA 5) NEED PANELS LABELED, AND NEED PANEL DIRECTORY FOR PANELS 6) QUAD OUTLET NEXT TO PANEL 110 NEEDS TO BE GFI 7) NEED WORKING CLEARANCE FOR PANELS |