Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/17/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 10/15/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GROUND ALL METAL BOXES 2. PROPERLY STRAP MC CABLE WITHIN 12" OF CONNECTORS AND EVERY 72" AFTER 3. BOXES OVERFILLED 4. LOW VOLTAGE CABLE THROUGH METAL STUDS TO BE PROTECTED FROM DAMAGE 5. RECALL WHEN CORRECTIONS MADE |