Permit: T08CM03268

Parcel: 141148180

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T08CM03268

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
10/17/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
10/15/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. GROUND ALL METAL BOXES
2. PROPERLY STRAP MC CABLE WITHIN 12" OF CONNECTORS AND EVERY 72" AFTER
3. BOXES OVERFILLED
4. LOW VOLTAGE CABLE THROUGH METAL STUDS TO BE PROTECTED FROM DAMAGE
5. RECALL WHEN CORRECTIONS MADE