Inspection History Details
Inspection Status: Approved
Inspection History: ENGINEERING - FINAL
Permit Number - T08CM03225
Inspection Description - ENGINEERING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/09/2010 | ENGINEERING - FINAL | Approved | ||
12/08/2009 | ENGINEERING - FINAL | Denied | SITE HAS ALREADY BEEN OCCUPIED PRIOR TO RECEIVING AN INSPECTION REQUEST. THE FOLLOWING SITE ITEMS MUST BE ADDRESSED PRIOR TO APPROVAL BY ENGINEERING: 1) PROVIDE A COPY OF DSMR 2-08.5.1A; DSMR-DS-08-60; AND DSMR 2-08.3.0 FOR INSPECTION AND FOR OUR RECORDS. 2) INSTALL ALL 6" DEPRESSED WATER HARVESTING AREAS SHOWN ON YOUR APPROVED PLANS. 3) ADDITIONAL SIDEWALK SCUPPERS WERE INSTALLED ALONG SOUTH AND EAST ACCESS POINTS NOT SHOWN ON THE APPROVED PLANS. 4) MAIN ACCESS ENTRANCE DRIVEWAY WAS NOT CONSTRUCTED PER THE APPROVED PLANS. 5) ROCK RIP RAP AREAS ALONG NORTH SIDE OF PROJECT WAS NOT CONSTRUCTED PER THE APPROVED PLANS - AREAS NEED TO MEET DIMENSIONS SHOWN ON THE PLANS AND INSTALL FILTER FABRIC UNDERNEATH ROCK. 6) NORTH PERIMETER FENCE MUST BE ELEVATED TO ALLOW FOR STORM WATER SITE DRAINAGE UNDER IT, SEE NOTE #6. 7) INSTALL VERTICAL CURBING WHERE SHOWN ON APPROVED PLANS - EXTRUDED CURBING WAS INSTALLED. |