Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESS TEST FNL
Permit Number - T08CM02847
Inspection Description - PLUMBING - GAS PRESS TEST FNL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/21/2009 | PLUMBING - GAS PRESS TEST FNL | Approved | IVRS - Inspection :* PLEASE READ ALL NOTES, CALL IN ALL PLUMBING INSPECTIONS FOR APPROVAL PRIOR TO FINAL INSPECTION. |
|
01/15/2009 | PLUMBING - GAS PRESS TEST FNL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. TEST THRU ANSUL VALVE TO APPLIANCE SHUT OFF VALVES 2. PROVIDE APPROVED GAS SHUTOFF VALVE AT ROOFTOP UNIT 3. PROVIDE BTU RATED FLEX AT ROOFTOP UNIT |