Permit: T08CM02740

Parcel: 115160320

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T08CM02740

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
10/06/2008 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
10/02/2008 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
09/19/2008 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
FLEX DUCT NOT PROPERLY SUPPORTED
SUPPORTS ARE NOT TO EXCEED 5'
STRAPS ARE TO BE MIN. 1.5 IN
PROVIDE COMPLETE WIRING AT AC-2
CONDENSATE PIPING CANNOT TERMINATE AT WASTE VENT