Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T08CM02740
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/06/2008 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
10/02/2008 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
09/19/2008 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* FLEX DUCT NOT PROPERLY SUPPORTED SUPPORTS ARE NOT TO EXCEED 5' STRAPS ARE TO BE MIN. 1.5 IN PROVIDE COMPLETE WIRING AT AC-2 CONDENSATE PIPING CANNOT TERMINATE AT WASTE VENT |