Permit: T08CM02517

Parcel: 12810064C


Addresses:

5411 E WILLIAMS BL


Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T08CM02517

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
10/27/2009 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
06/09/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
05/13/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK UG FOR FLAG POLE LIGHTS
05/12/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK U.G. FOR LIGHTING @ PATIO AREA
05/06/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK GEC FOR POWER CONDITIONER
05/05/2009 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
05/04/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK 2 BASES FOR BOLLARDS
05/01/2009 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
04/29/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
03/04/2009 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
1. OK WALLS RMS. 113, 107
2. OK XFMR GEC TO BUILDING STEEL FOR
XFMRS LAC, LCDF, LCUB, LTL1, LLAB
01/21/2009 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
01/15/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK GROUND LOOP @ TANK BUILDING
01/14/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. OK U.G TO TANK BUILDING
2. GROUND LOOP @ TANK BUILDING NEEDS TO BE INSPECTED
3. ALL GROUNDING ELECTRODES @ TANK BUILDING TO BE CONNECTED TOGETHER
01/12/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. OK CADWELD TO BUILDING STEEL FROM UFER
2. OK CADWELD TO BUILDING STEEL FOR CONNECTION TO SPRINKLER PIPE
3. OK 2 FLOOR BOXES
12/19/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
12/17/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. OK CONTINUATION OF 11 - 4" PVC FROM BUILDING LINE TO TEP XFMR. INSTALL WARNING RIBBON PER NEC 300.5
2. OK U.G FOR PANEL FEEDERS AND X-FMR
12/15/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. OK 11 - 4" PVC FROM SES TO EDGE OF
BUILDING 90' HEADING SOUTH
2. OK 1 - 1 1/4" PVC FROM SES TO EDGE OF
BUILDING 90' HEADING SOUTH
3. OK CONTINUATION OF 1 - 1 1/4" AND 1 - 1" PVC
4. OK 1 - 4" FOR TELEPHONE
5. OK 1 - 3/4" AND 1 - 1" PVC CONTINUED PAST BUILDING LINE
12/09/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
2 - 2 1/4 TRANSFORMERS LCUB LCOF
1 - 1' TEMP POWER
1 - 1' BOTH TO TANK ENCLOSURE
1 - 3/4 BOTH TO TANK ENCLOSURE
3 - LINE TO 8
8 - TO F