Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/23/2009 | FRAMING | Approved | IVRS - Inspection :* 1) OK TO SHEETROCK ALL AREAS |
|
| 09/04/2009 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) EXCEPT FLOOR HEAT 2) GROUND METAL BOXES & LIGHT BOXES, PROTECT WIRE IN PAN CAKE BOXES 3) PROTECT WIRES CLOSER THAN 1 1/4" TO FACE OF FRAME MEMBER 4) CLOTHES WASHER ADDED 5) REVISE PLAN TO REFLECT AS BUILT 6) PLUMBING TO KITCHEN SINK AND CLOTHES WASHER SUB STANDARD-SUBMIT DETAIL TO D.S.D. FOR APPROVAL 7) BATH EXHAUST FAN NOT CONNECTED 8) POST ADDRESS AT FRONT OF PROPERTY 9) PROTECT WIRES AT SERVICE PANEL AND SECURE WIRES WITHIN 12" |