Permit: T08CM02251

Parcel: 117120310


Addresses:

1 E CONGRESS ST

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
10/01/2008 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
09/25/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
SEE CORRECTIONS ON ACTIVITY #T08CM02341
09/05/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. SEAL ALL BRANCH TAPS WITH HARDCAST
PER MECH. SPEC. 3.05
2. PROVIDE VOLUME CONTROL ON TAPS IN HARD LID AREA PER NOTE M1.1