Permit: T08CM01986

Parcel: 12009317A


Addresses:

266 E MISSOURI ST

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
02/12/2009 ELECTRIC - CABLE DROP Approved
01/26/2009 ELECTRIC - CABLE DROP Partial Approval IVRS - Inspection :*
PLAN SHOWS GUTTER AT SES TO ACCOMODATE
FUTURE 200 AMP SERVICES. EXTEND GUTTER AS SHOWN ON PLAN OR PROVIDE LETTER FROM ENGINEER OF RECORD ACCEPTING GUTTER AS INSTALLED.

OK TO CLEAR TEC SUBJECT TO LETTER FROM ENGINEER
01/23/2009 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
See detailed listing on site.| 999*
BOND NEUTRAL & GROUND ELECTRODE CONDUCTOR PER PLAN, SIZE PER 250.66 AND 250.102
01/21/2009 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
See detailed listing on site.| 999*
REVISE PLAN TO REFLECT FIELD INSTALL OR INSTALL SERVICE PER APP. PLAN
01/15/2009 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
See detailed listing on site.| 999*
01/14/2009 ELECTRIC - CABLE DROP Not ready for Inspection IVRS - Inspection :*
12/02/2008 ELECTRIC - CABLE DROP Not ready for Inspection IVRS - Inspection :*